Why your power factor penalty keeps coming back

A power factor penalty that returns after an APFC panel is installed usually means the panel is no longer correcting properly. Capacitors lose capacity with age and heat, stages may not match the load, harmonics can damage the bank, the controller's CT may be misplaced, or the panel may overcorrect at light load. A site check finds the cause.

By Kulaina engineering team ·

Capacitors lose capacity

A capacitor that runs hot loses capacitance year by year. Measure the current drawn by each stage and compare it with the rating: a stage drawing much less than its rated current needs replacing.

Stages that don’t match the load

If the load has grown or changed since the panel was built, the controller may not have enough capacity, or the right step sizes, to follow it.

Harmonics

New VFDs or UPS systems can add harmonics that overheat standard capacitors. A detuned panel may be needed.

The controller is measuring the wrong current

The APFC relay’s CT must sit on the main incomer, upstream of the capacitor feeder, and be wired with the right polarity. If it is in the wrong place, or reversed, the controller cannot see the real power factor and switches the wrong stages.

Overcorrection at light load

When the load drops at night or on holidays, too many stages left in service push power factor leading. Where the electricity board bills in kVAh and counts leading reactive energy, a leading power factor costs as much as a lagging one, so check the controller’s switch-off settings.

What to do