Guide

How to size an APFC panel

To size an APFC panel, multiply the load in kW by the difference between the tangents of the present and target power factor angles. The result is the capacitor kVAR needed. Round up to a standard bank, split it into stages that match how the load changes, and add detuned reactors if harmonics are present.

By Kulaina engineering team ·

The formula

Required kVAR = load (kW) × (tan φ₁ − tan φ₂)

Here φ₁ is the angle of your present power factor and φ₂ the angle of the target. For a power factor PF, tan φ = √(1 − PF²) ÷ PF.

A worked example

A plant draws 400 kW at a power factor of 0.78 and wants 0.99.

Step Value
tan φ₁ at 0.78 0.802
tan φ₂ at 0.99 0.142
Difference 0.660
Required kVAR (400 × 0.660) 264 kVAR
Next standard bank 300 kVAR

Choosing the stages

The controller switches stages in and out to follow the load, so the smallest stage sets how finely it can correct. A 300 kVAR panel is often built as 1 × 25, 1 × 50 and 3 × 75 kVAR. If your load swings by small steps, use more, smaller stages.

When you need detuned reactors

VFDs, UPS systems, induction furnaces and other non-linear loads create harmonics. Harmonics can overload capacitors or cause resonance with the transformer. Detuned reactors, commonly 7% or 14%, protect the bank. A harmonic measurement during the site study tells you which you need.

Allow for growth and ageing

Add 10 to 20 percent if the load is expected to grow, and remember that capacitors lose capacity with age and heat.

For a quick estimate, try the kVAR calculator. Then send us your load data for a site-checked design.

Related products

Frequently asked questions

What target power factor should I design for?

Most designs aim for 0.99. Going beyond that adds capacitors for little benefit and risks a leading power factor at light load.

Can I size the panel from my electricity bill?

The bill gives a good first estimate of kW and average power factor. A site study adds the load profile and a harmonic measurement, which decide the stage sizes and whether you need detuned reactors.

Discuss your panel requirement

Send your single-line diagram, BOQ or tender reference. An engineer replies within one working day.