Skip to content
KULAINAAUTOMATION
Menu

Product

Solar ACDB panels

A solar ACDB, or AC distribution box, collects the AC output of one or more inverters and protects it before it reaches the building's LT panel or the grid. It houses the inverter breakers, surge protection devices and metering, and lets the solar plant be isolated safely for maintenance.

Specifications

Solar ACDB panels specifications
Inputs1 to 8 inverter inputs
ProtectionMCB or MCCB per inverter, Type 2 surge protection
MeteringMultifunction energy meter
EnclosureIP65 for outdoor mounting

Where it is used

  • Rooftop solar on factories and commercial buildings
  • Ground-mounted solar plants feeding an LT panel

Standards

IS 8623 · IEC 61439

Each ACDB is sized to the inverter ratings and the cable runs on site, and every incoming circuit is labelled, so the plant can be isolated safely before anyone works on it.

Frequently asked questions

What is the difference between a solar ACDB and a DCDB?

A DCDB sits between the solar panels and the inverter and handles DC. An ACDB sits after the inverter, on the AC side, and connects the plant to the building's supply or the grid.

Why does an ACDB need surge protection?

Lightning near the plant and switching on the grid send surges along the AC cables. Type 2 surge protection devices in the ACDB divert them to earth before they reach the inverter's AC output or the building's wiring. Surges picked up by the array itself are handled by the surge protection in the DCDB.

Discuss your panel requirement

Send your single-line diagram, BOQ or tender reference. An engineer replies within one working day.

Have drawings or a tender? Use the full enquiry form.